Perforated Cable Tray Drawings: How to Read Sections, Flanges & Dimensions

Perforated cable tray drawings help engineers, buyers and installers understand a product before manufacturing or installation. They communicate the tray profile, overall dimensions, reinforcement layout and perforation details.

Reading a drawing requires identifying both the dimension and the feature it measures. Overall tray width, reinforcement width, flange width and hole spacing describe different parts of the product.

This guide uses an ECTRAY reinforced perforated cable tray as a practical example. The supplied drawing shows a 300 mm overall tray width, 50 mm height and 272 mm bottom reinforcement width.

ECTRAY has also separately confirmed a 10 mm flange width and an available sheet thickness range of 0.6–1.5 mm. These additional specifications should be distinguished from dimensions shown in the supplied image.

What Do Perforated Cable Tray Drawings Show?

Different views explain different aspects of the product. Read them together to understand how the dimensions and features relate to one another.

Drawing viewInformation to review
Plan viewOverall width, length direction, perforations and reinforcement layout
Cross-section viewTray height, sidewall profile and local formed details
Side viewLongitudinal features and end details where shown
Detail viewEnlarged folds, reinforcement, holes or connection geometry
Assembly viewRelationship between the tray and matching components

Plan View: Width, Reinforcement and Perforations

The plan view shows the tray from above.

In the supplied example, 300 mm identifies the overall tray width, while 272 mm identifies the width of the stamped bottom reinforcement.

The plan view also shows repeated reinforcement features and the perforation arrangement along the tray length.

The 272 mm reinforcement width belongs to this illustrated 300 mm wide configuration. Other tray widths require their own confirmed reinforcement dimensions.

Cross-Section View: Height and Profile Details

The cross-section shows the tray profile across its width.

Use it to identify the base, sidewalls, folded edges and local profile details. The supplied example includes a 50 mm tray height and a 10 mm reinforcement-to-sidewall distance at the indicated location.

The separately confirmed 10 mm flange width is not dimensioned in this image.

This distinction is important: a visible profile feature and a confirmed specification are not necessarily the same as a dimension explicitly shown on the drawing.

Drawing Notes and Supporting Specifications

A product can be defined through both drawing dimensions and accompanying specifications.

Before reviewing individual measurements, check the product model, units, drawing number and revision. Then identify any information supplied separately, such as sheet thickness, flange width, material grade or finish.

For an approved order drawing, these sources should agree and clearly identify the required configuration.

perforated cable tray drawings

Dimensions Shown in the Drawing vs Additional Specifications

A professional drawing review separates information read directly from the drawing from information confirmed elsewhere.

For this ECTRAY example, the distinction is as follows:

ItemValueInformation source
Overall tray width300 mmShown in the supplied drawing
Tray height50 mmShown in the supplied drawing
Bottom reinforcement width272 mmShown in the plan view
Reinforcement-to-sidewall distance10 mmShown at the indicated section location
Hole diameterØ8.5 mmDimension meaning confirmed by ECTRAY
Transverse hole center spacing25 mmDimension meaning confirmed by ECTRAY
Longitudinal hole row center spacing50 mmDimension meaning confirmed by ECTRAY
Tray lengthLVariable shown in the drawing
Flange width10 mmSeparately confirmed; not dimensioned in the supplied image
Available sheet thickness0.6–1.5 mmSeparately confirmed manufacturing range

The flange width should be added to the applicable order drawing or associated specification where it is needed for manufacturing, inspection or accessory matching.

Overall Tray Width vs Reinforcement Width

The 300 mm and 272 mm dimensions describe different features.

Overall Tray Width: 300 mm

The 300 mm dimension identifies the overall width of the illustrated tray.

It describes the external product width between the indicated reference points. It should not automatically be treated as the clear space available for cables.

Where internal clearance is required, check a separately defined internal dimension.

The ETIM cable tray dimensional model identifies overall and internal dimensions separately. Check which measurement is specified before comparing tray sizes.

Bottom Reinforcement Width: 272 mm

The 272 mm dimension in the plan view identifies the width of the stamped bottom reinforcement.

It does not represent the overall tray width or internal clear width.

The correct description is:

A 300 mm wide perforated cable tray with a 272 mm bottom reinforcement width in the illustrated plan view.

Keeping these measurements separate prevents a local feature dimension from being mistaken for a product size.

Reinforcement Dimensions for Other Widths

The 272 mm reinforcement width applies to the illustrated 300 mm wide configuration.

Do not transfer it to every tray width or scale it proportionally without confirmation.

When reviewing perforated cable tray drawings for another size, use the corresponding product drawing and reinforcement dimensions.

Understanding the Two 10 mm Specifications

This example includes two different measurements with the same numerical value.

One is shown in the supplied drawing. The other was confirmed separately.

Drawing Dimension: Reinforcement-to-Sidewall Distance

The existing 10 mm dimension in the cross-section identifies the reinforcement-to-sidewall distance at the indicated location.

Read it using the reference points shown.

Do not replace it with a distance calculated by subtracting the 272 mm reinforcement width from the 300 mm overall width. Overall and local dimensions can reference different surfaces or feature boundaries.

Where these dimensions need to be checked together, use a detailed section with clearly defined reference points.

Additional Specification: Flange Width

ECTRAY has separately confirmed a 10 mm flange width.

This dimension is not marked in the supplied image. It should therefore be described as an additional product specification, rather than a measurement read from the screenshot.

For manufacturing or inspection, include the flange width in the approved drawing or associated specification.

Why the Distinction Matters

The two measurements should remain separately identified:

MeasurementValueStatus
Reinforcement-to-sidewall distance10 mmDimensioned in the supplied drawing
Flange width10 mmSeparately confirmed; not dimensioned in the supplied image

An identical value does not mean two dimensions describe the same feature.

How to Read Flanges and Folded Edges

In this guide, a flange means the folded edge of the tray profile. It should be distinguished from an end connection flange used in another design.

Identify the Folded Profile

Trace the section from the base along the sidewalls and folded edges.

Check the fold direction and whether the profile includes an additional return fold. Where the general view is unclear, request an enlarged detail.

The separately confirmed flange width for this example is 10 mm. The original image should not be presented as showing that dimension.

Flange Width vs Complete Fold Geometry

One width measurement does not fully define a folded profile.

Depending on the intended use of the drawing, additional information may be required for bend geometry, fold direction, return folds and dimensional tolerances.

These details are particularly useful where the folded edge interfaces with another component.

Check Covers and Fixing Components

Where a cover or clamp is required, compare its interface with the actual tray profile.

Review the flange geometry, cover dimensions and fixing arrangement together. Nominal tray width alone does not define the complete assembly.

An assembly section can clarify the relationship between the tray, cover and fixing components.

Tray Height, Length and Sheet Thickness

Height, length and thickness should be clearly assigned in the product documentation.

Tray Height: 50 mm

The section drawing specifies a 50 mm tray height.

This should be distinguished from usable internal depth. The base profile, folds and any features extending into the cable space need to be considered when defining internal clearance.

The supplied image does not fully establish the reinforcement height or forming direction. Confirm those details where internal depth needs to be assessed.

Tray Length: L

The symbol L represents manufactured tray length.

Its value should be assigned in the drawing notes, specification or order schedule. Do not estimate it from the displayed proportions of the image.

Tray length and support span are different:

TermMeaning
Tray lengthLength of one manufactured tray section
Support spanDistance between supports carrying the installed tray

A specified tray length does not establish an allowable support span.

Available Sheet Thickness: 0.6–1.5 mm

ECTRAY manufactures this reinforced tray design in sheet thicknesses from 0.6 to 1.5 mm.

This range describes available manufacturing options. Each order requires an exact selected thickness.

SpecificationInformation to confirm
Available thickness range0.6–1.5 mm
Order thicknessExact selected sheet thickness
MaterialRequired material grade
Surface finishSpecified coating or treatment
Measurement basisClarification of coating inclusion where applicable

The range should not be used in place of an order-specific value.

Reading the Stamped Bottom Reinforcement

The plan view shows repeated transverse reinforcement features along the tray base.

It explains their layout, while additional sections may be needed to define the formed profile completely.

Locate the Reinforcement Outline

Find the repeated formed outlines in the plan view.

For this 300 mm wide tray, the reinforcement width is 272 mm.

Keep that dimension associated with the reinforcement feature. It should not be relabeled as internal width or flange width.

Confirm Reinforcement Height and Forming Direction

A plan outline does not fully establish reinforcement height or forming direction.

A local section should clarify:

  • Reinforcement height or depth.
  • Direction relative to the cable space.
  • Local profile dimensions.
  • Transition geometry where required.
  • Relationship between perforations and formed areas.

These details connect the plan view with the actual manufactured shape.

Comparing Reinforced and Unreinforced Designs

To compare a reinforced tray with a tray without bottom reinforcement, use equivalent views and consistent dimension definitions.

Record overall dimensions, sheet thickness, folded profile, reinforcement geometry and perforation pattern separately.

Drawings explain structural differences. A comparison of working loads requires supporting information for the relevant configurations and support conditions.

Hole Diameter and Center-to-Center Spacing

Hole size and hole position describe different aspects of the perforation pattern.

A diameter defines the size of the indicated hole. Center-to-center spacing defines the position of one hole relative to another.

Hole Diameter: Ø8.5 mm

ECTRAY has confirmed that the 8.5 mm dimension specifies hole diameter.

In written specifications, it can be expressed as Ø8.5 mm. The diameter symbol distinguishes hole size from a linear spacing measurement.

The callout should clearly identify the feature to which the diameter applies. It should not be described as hole spacing or a hole-to-edge distance.

Transverse Hole Center-to-Center Spacing: 25 mm

The 25 mm dimension is the center-to-center distance between adjacent holes across the tray width.

It describes positioning rather than the clear gap between hole edges.

It also does not describe the distance from a hole center to the tray edge.

Longitudinal Hole Row Center-to-Center Spacing: 50 mm

The 50 mm dimension in the plan view describes the center-to-center spacing between adjacent hole rows along the tray length.

It should be distinguished from the separate 50 mm tray height dimension.

DimensionMeaning
Ø8.5 mmDiameter of the indicated hole
25 mmTransverse hole center-to-center spacing
50 mm in the plan viewLongitudinal hole row center-to-center spacing
50 mm in the cross-sectionTray height

The numerical value alone does not establish meaning. Read the associated view and dimension references.

Hole Spacing vs Edge Distance

Hole spacing measures the relationship between holes.

Edge distance locates a hole relative to a defined product edge.

In this example, 25 mm is hole center-to-center spacing. Any required hole-to-edge position needs its own dimension or an explicitly defined positioning scheme.

Worked Example: Reviewing the 300 mm Wide Tray

A structured review helps separate overall dimensions, local features and additional specifications.

Step 1: Confirm the Product Size

Identify the 300 mm overall width and 50 mm height shown in the drawing.

Locate L and check the associated documentation for its assigned value.

Keep overall dimensions separate from internal clearances and reinforcement dimensions.

Step 2: Review the Reinforcement

Locate the 272 mm reinforcement width in the plan view.

Then review the drawing’s 10 mm reinforcement-to-sidewall distance using its indicated reference points.

Confirm that the drawing corresponds to the required tray width before applying these dimensions.

Step 3: Record the Additional Flange Specification

Record the separately confirmed 10 mm flange width.

Because it is not dimensioned in the supplied image, add it to the order drawing or supporting specification where required.

Do not identify the existing 10 mm drawing callout as flange width.

Step 4: Separate Hole Size from Hole Position

Read Ø8.5 mm as hole diameter.

Read 25 mm as transverse hole center-to-center spacing and 50 mm as longitudinal hole row center-to-center spacing.

This separates the size of the indicated hole from its position within the pattern.

Step 5: Confirm Thickness and Missing Details

Select the exact sheet thickness within the available 0.6–1.5 mm range.

Then confirm any required information not established by the image, including:

  • Assigned tray length.
  • Material grade and surface finish.
  • Flange detail and complete fold geometry.
  • Reinforcement height and forming direction.
  • Complete geometry of each opening type.
  • End connection details.
  • Dimensional tolerances.
  • Drawing number, revision and approval status.

A drawing review should record both confirmed information and unresolved requirements.

Connection Details and Matching Accessories

Perforated cable tray drawings should be reviewed with the components needed to join and complete the route.

End Holes and Splice Plates

Compare tray end details with the matching splice plate drawing.

Check hole dimensions, center spacing, distance from the tray end and specified fasteners.

The bottom perforation arrangement should not be assumed to define the end connection pattern.

Covers and Dividers

Review fixing positions against the actual tray profile.

Check for interference with folded edges, reinforcement features and connection hardware.

An assembly drawing is useful where several parts share the same fixing area.

Bends, Tees and Reducers

For fittings, confirm the interface dimensions at each connection.

Review widths, heights, directions and joint details together. Matching nominal sizes should be checked against the actual profile and connection arrangement.

Common Mistakes When Reading Perforated Cable Tray Drawings

Confusing Tray Width with Reinforcement Width

The 300 mm dimension describes overall tray width.

The 272 mm dimension describes reinforcement width in the plan view. It does not establish internal clear width.

Confusing the Two 10 mm Measurements

The existing 10 mm drawing dimension identifies reinforcement-to-sidewall distance.

The separately confirmed 10 mm flange width is not dimensioned in the supplied image.

Keep their descriptions and information sources separate.

Presenting Additional Specifications as Drawing Callouts

A confirmed product specification can be valid even when it is absent from an illustration.

However, the article, quotation and inspection documents should state whether the information comes from the drawing or an additional specification.

Applying One Reinforcement Width to Every Tray Size

The 272 mm value belongs to the illustrated 300 mm wide configuration.

Other widths require their own confirmed dimensions.

Confusing Hole Diameter with Hole Spacing

Ø8.5 mm describes hole size.

The 25 mm and 50 mm perforation dimensions describe center-to-center positioning.

Treating a Thickness Range as an Order Instruction

The 0.6–1.5 mm range describes available manufacturing options.

Each order requires an exact selected thickness.

Measuring a Screenshot

A screenshot may be resized, cropped or displayed at an unknown scale.

Use stated dimensions and approved drawing data. Request missing measurements rather than estimating them from the image.

Assuming Geometry Establishes Load Capacity

A drawing describes product geometry.

It does not independently establish an allowable working load at a proposed support span. Review the relevant material, thickness, support conditions and performance documentation before making a load claim.

For cable tray and cable ladder system requirements and testing, consult IEC 61537. The standard reference alone does not establish the load capacity of the illustrated product.

Checklist Before Approving Perforated Cable Tray Drawings

Review itemInformation to confirm
Drawing identificationModel, drawing number, revision and approval status
UnitsApplicable units and any exceptions
Overall dimensionsWidth, height and assigned length
Internal clearancesClear width and depth where required
Sheet thicknessExact selected thickness
Material and finishRequired grade and surface treatment
Drawing dimensionsFeatures and measurement references clearly identified
Additional specificationsSeparately confirmed values incorporated where required
FlangesWidth and complete geometry where required
ReinforcementDimensions applicable to the selected tray width
Hole sizeDiameter and complete geometry of each opening type
Hole positioningCenter-to-center spacing and required edge distances
ConnectionsEnd holes, splice plates and fasteners
AccessoriesMatching covers, dividers and fittings
TolerancesAcceptance limits for relevant dimensions
PerformanceSeparate information for the intended load and support arrangement

The objective is a consistent product definition that purchasing, manufacturing and inspection can follow.

Discuss Your Cable Tray Drawing Requirements with ECTRAY

ECTRAY offers perforated cable tray designs with and without stamped bottom reinforcement.

Reinforced designs are available in sheet thicknesses from 0.6 to 1.5 mm. Dimensions, flange details and reinforcement geometry should be confirmed for the selected configuration.

For a quotation or drawing review, provide:

  • Required width, height and length.
  • Selected sheet thickness.
  • Material and surface finish.
  • Preferred bottom structure.
  • Flange, perforation and connection requirements.
  • Required covers, dividers and fittings.
  • Proposed support span and cable loading where performance review is needed.

Share your drawing or marked-up specification with ECTRAY to clarify the product profile and matching components before ordering.

Frequently Asked Questions

What Is the Tray Size in This Example?

The supplied drawing shows a tray with a 300 mm overall width and a 50 mm height.

What Does the 272 mm Dimension Represent?

It identifies the bottom reinforcement width in the plan view of the 300 mm wide tray. It does not represent internal clear width.

What Does the Existing 10 mm Drawing Dimension Represent?

It identifies the reinforcement-to-sidewall distance at the indicated location.

Is the 10 mm Flange Width Shown in the Image?

No. ECTRAY separately confirmed a flange width of 10 mm. It is not dimensioned in the supplied image and should be added to the applicable order documentation where required.

Does Every Tray Width Use a 272 mm Reinforcement?

No. The 272 mm value applies to the illustrated 300 mm wide configuration. Check the corresponding drawing for other widths.

What Thicknesses Are Available for the Reinforced Design?

The available sheet thickness range is 0.6–1.5 mm. The exact order thickness should be specified separately.

What Does Ø8.5 mm Mean?

It specifies the diameter of the indicated hole.

What Does the 25 mm Dimension Mean?

It is the center-to-center distance between adjacent holes across the tray width. It is not a hole-to-edge distance or a clear gap between hole edges.

Why Are There Two 50 mm Dimensions?

The cross-section uses 50 mm for tray height. The plan view uses 50 mm for longitudinal hole row center-to-center spacing.

Does L Represent Support Span?

No. L represents manufactured tray length. Support span is the distance between installed supports.

Can Load Capacity Be Determined from the Drawing Alone?

No. A working load assessment also requires the relevant material, sheet thickness, support conditions and performance documentation.

Share As: